Fault Codes, Powerflex 4/40
Fault | Explanation |
---|---|
F2 | Auxiliary Input – Auxiliary input interlock is open |
F3 | Power Loss – DC bus voltage is below 85% of nominal |
F4 | UnderVoltage – DC bus voltage is below minimum value |
F5 | OverVoltage – DC bus voltage is over maximum value |
F6 | Motor Stalled – Drive is not able to accelerate motor |
F7 | Motor Overload – Internal electronic overload trip |
F8 | Heatsink Overtemp – Heatsink temperature exceeds set value |
F12 | HW OverCurrent – The drive output current has exceeded the hardware current limit |
F13 | Ground Fault – A current path to ground has been detected at one or more output terminals |
F29 | Analog Input Loss – A signal loss at an analog input has occurred |
F33 | Auto Restart Tries – Drive failed to reset a fault and resume running |
F38 | Phase U to Ground – A phase to ground fault has been detected in this phase |
F39 | Phase V to Ground – A phase to ground fault has been detected in this phase |
F40 | Phase W to Ground – A phase to ground fault has been detected in this phase |
F41 | Phase UV Short – Excessive current has been detected between these two output terminals |
F42 | Phase UW Short – Excessive current has been detected between these two output terminals |
F43 | Phase VW Short – Excessive current has been detected between these two output terminals |
F48 | Parameters Defaulted – Drive was commanded to write default values to EEPROM |
F63 | SW OverCurrent – Programmed current trip has been exceeded |
F64 | Drive Overload – Drive rating of 150% for 1 minute or 200% for 3 seconds exceeded |
F70 | Power Unit – Failure has been detected in the drive power section |
F71 | Net Loss – The communication network has faulted |
F80 | SVC Autotune – Autotune function has failed or was cancelled by the user |
F81 | Comm Loss – RS485 (DSI) port has stopped communicating |
F100 | Parameter Checksum – The checksum read does not match the checksum calculated |
F122 | I/O Board Fail – Failure has been detected in the drive control and I/O section |
Manuals
Powerflex "Quick Start" guide, noting the basic wiring and programming for a basic setup: File:Powerflex 4-40 Quick.pdf
Powerflex 4 User's Manual: File:AB Powerflex 4 UM.pdf
Powerflex 40 User's Manual: File:AB PowerFlex 40 UM.pdf